Okuma OSP 5000L-G, 5020, 5020L, 700L, 7000L RS-232 Parameters
Controls
- OSP5000L-G
- OSP5020
- OSP5020L
- OSP700L
- OSP7000L
Notate or take a picture of any parameters before you change them
Change Okuma Parameters
- Ensure the NC PANEL key is set to "UNLOCK"
- Press PARAMETER button
- Press ITEM DOWN (F7) softkey until you get to "OPTIONAL PARAMETER WORD"
- Change the following parameters
PAGE UP and PAGE DOWN keys to navigate between "OPTIONAL PARAMETER WORD" pages
To change the parameter, highlight the value, press SET, type in new value, then press WRITE button
- #1 = 1 (Feed Holes)
- #34 = 30 (Busy Time)
- #39 = 4800 (Baud Rate)
- #44 = 0 (Punch Port)
- #54 = 1 (Read Port)
- Press ITEM DOWN (F7) softkey until you get to "OPTIONAL PARAMETER BIT"
- Change the following parameters
PAGE UP and PAGE DOWN keys to navigate between "OPTIONAL PARAMETER WORD" pages
To change the parameter, highlight the bit, press SET, type in new bit, then press WRITE button- #1 = 00011011
- #12 = 10101011
- Reboot control
Alternative Parameters
The following set of parameters have been known to work. Try these if the above parameters do not work.
- Alternative 1
- OPTIONAL PARAMETER BIT
- #1 = 00000000
- #12 = 10101010
- Alternative 2
- OPTIONAL PARAMETER BIT
- #1 = 01011011
- #12 = 10100010
- Alternative 3
- OPTIONAL PARAMETER BIT
- #1 = 00001011
- #12 = 10101010
PC Settings
- Baud Rate = 4800
- Data Bits = 7
- Parity = Even
- Stop Bits = 1
- Flow Control = Xon/Xoff
Troubleshooting
- Parameter changes are not retained after reboot
- Wait about 5 minutes after changing the last parameter
- Power off NC
- Wait about 2 minutes
- Power on NC and verify changes stuck