Fanuc 0 RS-232 Parameters

Fanuc 0 RS-232 Parameters

Controls

  1. Fanuc 0M, 0T
Warning
Notate or take a picture of any parameters before you change them

Change Fanuc Parameters

  1. Put control in MDI mode
  2. Press DGNOS PARAM button until you see "PARAMETER" page
  3. Press PARAM softkey
  4. On SETTING 1 page, change the following
    1. Set ISO to "1"
    2. Set I/O to "0" for port 0 or "1" for port 1
  5. Press PAGE DOWN
  6. On SETTING 2 page, change the following
    1. Set PWE to "1"
  7. Press PAGE DOWN to find and change the following parameters
  8. InfoTo change a bit, you must enter all bits, then press INPUT
    1. 0002 to "1XXXX0X1" ("X" means do not change)
    2. 0038 to "1010XXXX"
    3. 0055 to "XXXXX000"
    4. 0070 to "0XXXXXXX"
    5. 0552 to one of the following
      1. Set to "11" for 9600 baud
      2. Set to "10" for 4800 baud
      3. Set to "9" for 2400 baud
      4. Set to "8" for 1200 baud
      5. Set to "7" for 600 baud
  9. Go back to SETTING 2 page and change PWE back to 0
  10. Press RESET to clear any alarms
Info
If the program is unable to load, try changing parameter 0038 to "1001XXXX". If that still does not work, try changing 0038 one more time to "10001000"
    • Related Articles

    • Haas RS-232 Parameters

      Controls Any Haas with a RS-232 Port (usually 2016 or older, formally called Classic Haas Control or CHC) Notate or take a picture of any parameters before you change them Set Parameters Standard Transfers (Default) Press SETNG GRAPH button Press ...
    • Fanuc 16, 18, 21, 0i, 30i, 31i, 32i RS-232 Parameters

      Controls Fanuc 16-M, 16-T, 16i-M, 16i-T, 16i-MB, 16i-TB, 160i-MB, 160i-TB, 160is-MB, 160is-TB Fanuc 18-M, 18-T, 18i-M, 18i-T, 18i-MB, 18i-TB, 180i-MB, 180i-TB, 180is-MB, 180is-TB Fanuc 21-M, 21-T, 21i-M, 21i-T, 21i-MB, 21i-TB, 210i-MB, 210i-TB, ...
    • Siemens 802D RS-232 Parameters

      Controls Siemens 802D Notate or take a picture of any parameters before you change them Change Siemens 802D Parameters Press Menu Select button Press Services softkey Press Devices softkey Select Standard interface from top Press Copy to clipboard ...
    • Okuma OSP P100, P200, P300 RS-232 Parameters

      Controls OSP-P100L, OSP-P100M OSP-P200L, OSP-P200M, OSP-P200S, OSP-P200LA, OSP-P200MA, OSP-P200SA OSP-P300L, OSP-P300M, OSP-P300S, OSP-P300LA, OSP-P300MA, OSP-P300SA Notate or take a picture of any parameters before you change them Set Tape Puncher ...
    • Siemens 810D Powerline RS-232 Parameters

      Controls Siemens 810D Powerline Notate or take a picture of any parameters before you change them Change Siemens 802D Parameters Press MENU SELECT button Press SERVICES Press SET Set the following parameters Interface to “COM1” Protocol to “XON/XOFF” ...